@article {10.3844/ajassp.2006.1990.1992, article_type = {journal}, title = {Comparison of Losses and Flux Distribution in 3 Phase 100 kVA Distribution Transformers Assembled from Various Type of T-Joint Geometry}, author = {Daut, I. and Ahmad, Dina M.M. and Zakaria, S. and Uthman, S. and Taib, S.}, volume = {3}, year = {2009}, month = {Dec}, pages = {1990-1992}, doi = {10.3844/ajassp.2006.1990.1992}, url = {https://thescipub.com/abstract/ajassp.2006.1990.1992}, abstract = {This paper describes results of an investigation of the variation of power loss, building factor, flux leakage and flux distribution in 3-phase model transformer cores assembled from various type of T-joint geometry. The loss of the core with T-joint 60o was 10%, 12% and 15% better than the core with T-joint 45o, T-joint 23o and T-joint 90o respectively and 1.7 T, 50 Hz. The flux lines showed that flux penetration into the central limb was an important factor in causing the differences in performance.}, journal = {American Journal of Applied Sciences}, publisher = {Science Publications} }